Thermal resistance
Treat heat flow like electric current — add the resistances of layers and air films to find heat loss and U-values.
0 deeper section(s) hidden.
On this page
The idea
Heat flow behaves like electric current: a temperature difference drives it and a R holds it back, Q̇ = ΔT/R. A layer of material has R = L/(kA); an air film on a surface has R = 1/(hA). Layers that heat must pass through one after another are in series, so their resistances simply add. The result is often given as a .
Everyday intuition
Like water flowing through a row of narrow pipes, the narrowest one limits the flow most. In a wall the insulation layer is the narrow pipe: it sets the heat loss almost by itself.
How it works
- Draw the path. Inside air → inside surface film → each layer → outside surface film → outside air.
- Work out each resistance (in K/W): L/(kA) for each layer, 1/(hA) for each air film. Per square metre, use A = 1.
- Add them in series: R_total = R₁ + R₂ + …; then Q̇ = (T_inside − T_outside)/R_total.
- Temperatures at each interface follow from the same Q̇: each layer’s temperature drop is Q̇ × its R, so the biggest resistance takes the biggest drop.
- U-value = 1/(R_total A), in W/(m²·K): the heat lost per square metre per kelvin of difference. Lower is better for insulation.
- Parallel paths (a window in a wall, a timber stud in insulation) carry heat side by side; there you add conductances (1/R) instead.
The same heat flows through all of them; the largest resistance takes the largest temperature drop.
Interactive lab
Heat flow through a layered wall
- Set the middle layer thickness to 0: the heat loss jumps, and the inside surface gets cold enough for condensation.
- Double the insulation: the loss nearly halves. Doubling the brick changes very little.
- Turn the wind up from 0 to 20 m/s: for an insulated wall the loss hardly changes, because the outside air film is a small resistance.
- The steepest part of the temperature profile is in the layer with the largest resistance.
Temperature (°C) through the wall, inside (left) to outside (right), position in mm
- U-value
- —
- Heat loss per m²
- —
- Inside surface temperature
- —
- Total resistance (per m²)
- —
- Largest resistance
- —
Model assumptions and limits
- Steady, one-dimensional heat flow through 1 m² of wall; no air leaks, moisture or thermal bridges.
- Inside film h = 7.7 W/(m²·K). Outside film from wind speed by the simple fit h = 5.7 + 3.8 v (W/(m²·K), v in m/s); radiation is folded into both films.
- Conductivities are typical values (W/(m·K)): brick 0.72, concrete 1.4, mineral wool 0.04, expanded polystyrene 0.035, timber 0.13, plasterboard 0.21, glass 0.8. Real products vary.
- The condensation warning uses a rough threshold of 12.5 °C for the inside surface (about the dew point of air at 20 °C and 60% relative humidity).
Key formulas
Thermal resistances:
Layers in series and the U-value:
- thermal resistance K/W
- total resistance of all layers and films K/W
- overall heat transfer coefficient (U-value) W/(m²·K)
Worked example
Where it is used
- Building regulations set maximum U-values for walls, roofs and windows.
- Electronics cooling: chip-to-air resistance (junction, paste, heat sink, air) decides the chip temperature.
- Pipe insulation: the same idea, with curved layers, sets how thick lagging must be.
- Condensation checks: interface temperatures show where moisture in a wall could condense.
Common misconceptions
Self-check
Check Three layers have R = 0.1, 2.0 and 0.2 K/W. What is the total, and which layer has the largest temperature drop?
Show answer
2.3 K/W; the 2.0 K/W layer.
Check What is the U-value of a wall with R_total = 2.5 m²·K/W (per square metre)?
Show answer
U = 1/2.5 = 0.4 W/(m²·K).
Check Why does a draught make a well-insulated wall perform worse than its U-value says?
Show answer
Air leaking through carries heat by convection, bypassing the resistances in the calculation.