Refrigerators and heat pumps
How the vapour-compression cycle moves heat from cold to hot, what COP means, and why heat pumps beat electric heaters.
0 deeper section(s) hidden.
On this page
The idea
A refrigerator moves heat from a cold space to a warmer one, which the second law allows only with work input. The vapour-compression cycle does it with a that boils at a low temperature: it boils inside the fridge, absorbing heat, is compressed, then condenses outside, releasing heat. Performance is measured by the — heat moved per unit of work — which is usually well above 1. A is the same machine used for heating.
Everyday intuition
Sweat cools you because evaporating water takes heat from your skin. A fridge does the same with a refrigerant, then uses a compressor to squeeze the vapour so it can give that heat away to the room.
How it works
- 1→2 compressor: low-pressure vapour is compressed; its pressure and temperature rise above the room’s.
- 2→3 condenser: the hot vapour gives heat Q_h to the room (the warm grille at the back) and condenses to liquid.
- 3→4 : the liquid passes a restriction; its pressure drops and part of it flashes to vapour, becoming very cold.
- 4→1 evaporator: the cold mixture boils inside the fridge, taking heat Q_c from the food.
- Energy balance: Q_h = Q_c + W. COP_R = Q_c/W for cooling; COP_HP = Q_h/W = COP_R + 1 for heating.
- Carnot limit: COP_R ≤ T_c/(T_h − T_c). The smaller the temperature lift, the higher the COP.
The refrigerant loop and its states 1–4.
Key formulas
Coefficient of performance:
Best possible COP (Carnot):
- heat removed from the cold space J
- heat delivered to the warm side J
- work input J
- cold and warm temperatures K
Worked example
Where it is used
- Food and medicine cold chains: fridges, freezers, refrigerated lorries.
- Air conditioning: the same cycle, with the evaporator indoors.
- Home heating: heat pumps deliver about 3 kWh of heat per kWh of electricity, three times an electric heater.
Common misconceptions
Self-check
Check A heat pump delivers 9 kW of heat using 3 kW. What is its COP?
Show answer
COP_HP = 9/3 = 3.
Check What does the expansion valve do?
Show answer
Drops the refrigerant pressure so it becomes cold enough to absorb heat in the evaporator.
Check Best possible COP of a fridge at −3 °C rejecting heat at 27 °C?
Show answer
T_c/(T_h − T_c) = 270.15/30 ≈ 9.