Module 5 · Heat transfer

Heat exchangers

Devices that pass heat from one fluid to another — parallel and counterflow, the overall U and the log-mean temperature difference.

Notes
On this page
  1. The idea
  2. Everyday intuition
  3. How it works
  4. Key formulas
  5. Worked example
  6. Where it is used
  7. Common misconceptions
  8. Self-check

The idea

A moves heat from a hot fluid to a cold one through a wall, without letting them mix. The heat rate is set by an energy balance on each stream and by Q̇ = UA ΔT_lm, where U is the overall coefficient and ΔT_lm the . Running the streams in opposite directions () gets the most out of a given area.

Everyday intuition

Two people walking past each other in opposite directions, passing a bucket of warm water back along the line: the cold stream keeps meeting hotter fluid, so it can end up warmer than the hot stream leaves.

How it works

  1. Energy balance. Heat lost by the hot stream = heat gained by the cold stream: Q̇ = ṁ_h c_p,h ΔT_h = ṁ_c c_p,c ΔT_c (if no heat leaks out).
  2. Overall coefficient U. The wall and the two fluid films are resistances in series: 1/U = 1/h_hot + wall + 1/h_cold (+ fouling). Typical U: water to water 800–1 500 W/(m²·K), gas to gas 10–50.
  3. Why a log mean? The temperature difference changes along the exchanger. Averaging it properly over the length gives ΔT_lm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂).
  4. vs counterflow. In parallel flow both streams enter at the same end and their temperatures approach each other; the cold outlet can never exceed the hot outlet. Counterflow keeps a more even ΔT and can do more with the same area.
  5. Types. Shell-and-tube (refineries, power plants), plate (dairies, heat pumps, district heating), finned-tube (car radiators, air conditioners).
  6. — scale, rust and biological growth on the surfaces — adds resistance over time, so designers add extra area.
hot → cold → (parallel flow) hot → ← cold (counterflow)

Counterflow — they enter at opposite ends and the temperature gap stays more even.

Parallel flow against counterflow. Tap each arrangement. Parallel flow and counterflow. Original diagram drawn for this site. Tap labelled parts for an explanation.
Parallel flow and counterflow

Key formulas

Heat exchanger duty and log-mean temperature difference:

Q˙=UA ΔTlmΔTlm=ΔT1−ΔT2ln⁡(ΔT1/ΔT2)\dot Q = U A\,\Delta T_{lm} \qquad \Delta T_{lm} = \dfrac{\Delta T_1 - \Delta T_2}{\ln(\Delta T_1/\Delta T_2)}
ΔT1, ΔT2\Delta T_1,\ \Delta T_2
temperature differences at the two ends K
ΔTlm\Delta T_{lm}
log-mean temperature difference K

Worked example

Where it is used

  • Car radiators: hot coolant gives heat to air flowing through finned tubes.
  • Power plants: boilers, condensers and feedwater heaters are all heat exchangers.
  • Heat-recovery ventilators: outgoing warm air preheats incoming fresh air.
  • Refrigerators and heat pumps: the evaporator and condenser.

Common misconceptions

Self-check

Check Why is counterflow usually preferred?

Show answer

It keeps a more uniform temperature difference, so it transfers more heat for the same area and lets the cold stream leave hotter.

Check If both end temperature differences are equal (say 30 K), what is ΔT_lm?

Show answer

30 K; the log mean equals the common value.

Check What does fouling do to U and to the required area?

Show answer

It adds resistance, lowering U, so more area is needed for the same duty.